San Jose, CA
Specially trained, highly experienced system and network engineering staff actively manage and maintain the facility 24 hours a day, 7 days a week, 365 days a year. This is one of the first commercially available facilities in the world with a three-factor security access requirement.
In this facility, Hyve offers co-location and fully managed hosting solutions, as well as direct access to multiple network providers including AboveNet, DataPipe, Level 3, MCI, SBC and XO.
Custom Design
- HIPAA compliant
- 117,798 square foot facility
- 67,846 square feet of raised floor
- Entire structure meets Bellcore Network Equipment Building Systems Requirements
- Carrier neutral facility fed by multiple Tier 1 providers, via redundant MPOE fiber vaults
- Hyve network featuring redundant fiber sources, aggregate switches and core routers
- VESDA smoke detection systems, above and below raised floor
- Dual interlock pre-action dry-pipe fire suppression system (two events required to activate)
- California Category Four earthquake compliant
Security
- 24/7 on-site building and network monitoring
- 24/7 security staff, strictly enforced security procedures
- Colo exterior radius structure meets Level III / explosion resistance security standards
- One of the first facilities to implement true three factor security
- Visitors are escorted by authorized personnel at all times
- 24 hour internal and external video surveillance, 60-day minimum retention policy
- Multiple mantraps with reinforced walls
Power Conditioning
- Facility fed by multiple power grids
- Pre-negotiated one-hour advanced notice contact for any pending rotating block outages
- Five HiTec rotary flywheel Uninterruptible power supply (UPS) system N+2 architecture
- Five HiTec generators rated at 1.8 megawatts each with 20,000 gallons of fuel capacity
- Contracted fuel suppliers on call 24 hours a day, seven days a week
- 75 watts per square foot
- 22 PDUs located throughout the data center rated at 225kva each
HVAC Temperature Controlled Environment
- 367 BTUs of cooling per square foot
- Temperature range of 72 +/- 5 degrees Fahrenheit
- Relative humidity range from 40% – 60% RH
- 71 CRAC units rated at 22 tons of cooling, utilizing DX, R-22 refrigerant
- Raised floor to provide uniform cooling distribution